错误 #15730
+1设备报警管理--组合空调夏季停机状态水阀开度异常应该恢复的时候没有恢复
0%
描述
1.进入设备报警管理
2.查看组合空调夏季停机状态水阀开度异常设备报警
问题:在某个时刻应该恢复,后边如果满足报警条件再重新产生报警,但是现在是在这个时刻点没有恢复而是这条报警一直持续
文件
历史记录
由 李兴 更新于 超过 2 年 之前
没有接收到10点半的数据
2021-12-23 10:11:47.689 DEBUG [org.springframework.amqp.rabbit.RabbitListenerEndpointContainer#0-335] c.p.s.impl.AlarmHandleServiceImpl 接收到采集值:[[{"dataTime":"20211223094500","meterId":"Eq32060200013a235b6e9bb34517bbb4401c04c0e3b2","itemCode":"Eqdx006","funcId":["ACATAH_ReturnAirValveOpening","ACATAH_RunStatus","ACATAH_SupplyFanFreq"],"value":[149.99865,0.0,157.0]}]]
2021-12-23 10:11:47.690 DEBUG [pool-2-thread-19] c.p.s.impl.AlarmHandleServiceImpl 设备id: Eq32060200013a235b6e9bb34517bbb4401c04c0e3b2, 报警类型: Eqdx006, 监测指标:["ACATAH_ReturnAirValveOpening","ACATAH_RunStatus","ACATAH_SupplyFanFreq"],采集值:[149.99865,0.0,157.0], 采集时间:20211223094500
2021-12-23 10:11:47.691 DEBUG [pool-2-thread-19] c.p.s.impl.AlarmHandleServiceImpl triggerResult:[true],endResult:[false]
2021-12-23 10:11:47.691 DEBUG [pool-2-thread-19] c.p.s.impl.AlarmHandleServiceImpl 满足报警条件
2021-12-23 10:11:47.691 DEBUG [pool-2-thread-19] com.persagy.cache.AlarmRedisCache alarmDefineState: [0], ( 0-正常 1-报警)
2021-12-23 10:11:47.691 DEBUG [pool-2-thread-19] c.p.s.impl.AlarmHandleServiceImpl 报警持续时间:[0]¶
2021-12-23 10:26:46.103 DEBUG [org.springframework.amqp.rabbit.RabbitListenerEndpointContainer#0-340] c.p.s.impl.AlarmHandleServiceImpl 接收到采集值:[[{"dataTime":"20211223100000","meterId":"Eq32060200013a235b6e9bb34517bbb4401c04c0e3b2","itemCode":"Eqdx006","funcId":["ACATAH_ReturnAirValveOpening","ACATAH_RunStatus","ACATAH_SupplyFanFreq"],"value":[110.33,0.0,110.33]}]]
2021-12-23 10:26:46.104 DEBUG [pool-2-thread-17] c.p.s.impl.AlarmHandleServiceImpl 设备id: Eq32060200013a235b6e9bb34517bbb4401c04c0e3b2, 报警类型: Eqdx006, 监测指标:["ACATAH_ReturnAirValveOpening","ACATAH_RunStatus","ACATAH_SupplyFanFreq"],采集值:[110.33,0.0,110.33], 采集时间:20211223100000
2021-12-23 10:26:46.105 DEBUG [pool-2-thread-17] c.p.s.impl.AlarmHandleServiceImpl triggerResult:[true],endResult:[false]
2021-12-23 10:26:46.105 DEBUG [pool-2-thread-17] c.p.s.impl.AlarmHandleServiceImpl 满足报警条件
2021-12-23 10:26:46.105 DEBUG [pool-2-thread-17] com.persagy.cache.AlarmRedisCache alarmDefineState: [0], ( 0-正常 1-报警)
2021-12-23 10:26:46.105 DEBUG [pool-2-thread-17] c.p.s.impl.AlarmHandleServiceImpl 报警持续时间:[900]¶
2021-12-23 11:11:42.671 DEBUG [org.springframework.amqp.rabbit.RabbitListenerEndpointContainer#0-338] c.p.s.impl.AlarmHandleServiceImpl 接收到采集值:[[{"dataTime":"20211223104500","meterId":"Eq32060200013a235b6e9bb34517bbb4401c04c0e3b2","itemCode":"Eqdx006","funcId":["ACATAH_ReturnAirValveOpening","ACATAH_RunStatus","ACATAH_SupplyFanFreq"],"value":[157.0,0.0,157.0]}]]
2021-12-23 11:11:42.671 DEBUG [pool-2-thread-18] c.p.s.impl.AlarmHandleServiceImpl 设备id: Eq32060200013a235b6e9bb34517bbb4401c04c0e3b2, 报警类型: Eqdx006, 监测指标:["ACATAH_ReturnAirValveOpening","ACATAH_RunStatus","ACATAH_SupplyFanFreq"],采集值:[157.0,0.0,157.0], 采集时间:20211223104500
2021-12-23 11:11:42.672 DEBUG [pool-2-thread-18] c.p.s.impl.AlarmHandleServiceImpl triggerResult:[true],endResult:[false]
2021-12-23 11:11:42.672 DEBUG [pool-2-thread-18] c.p.s.impl.AlarmHandleServiceImpl 满足报警条件
2021-12-23 11:11:42.673 DEBUG [pool-2-thread-18] com.persagy.cache.AlarmRedisCache alarmDefineState: [1], ( 0-正常 1-报警)
2021-12-23 11:11:42.675 DEBUG [org.springframework.amqp.rabbit.RabbitListenerEndpointContainer#0-342] c.p.s.impl.AlarmHandleServiceImpl 接收到采集值:[[{"dataTime":"20211223104500","meterId":"Eq32060200013a235b6e9bb34517bbb4401c04c0e3b2","itemCode":"Eqdx007","funcId":["ACATAH_FreshAirValveOpening","ACATAH_RunStatus","ACATAH_SupplyFanFreq"],"value":[163.0,0.0,157.0]}]]
由 于明辉 更新于 超过 2 年 之前
- 文件 这个点应该恢复.png 这个点应该恢复.png 已添加
- 主题 从 设备报警管理--组合空调夏季停机状态水阀开度异常应该恢复的时候没有恢复 变更为 +1设备报警管理--组合空调夏季停机状态水阀开度异常应该恢复的时候没有恢复
- 状态 从 已解决 变更为 重新打开